,Capaccio Environmental Engineering, Inc.

"Helping Industry and the Environment Prosper"

293 Boston Post Road West
Marlborough, MA 01752
(508) 970-0033
Home About Us Services Tools

 

Environmental, Health and Safety Articles

October is Fire Safety Month
Healthcare Facility Fire Prevention Plans and
Select Fire Code Requirements

October 2009

As October is Fire Safety Month, it is an ideal time to point out a specific OSHA standard that is often overlooked and some specific fire code items that may be of interest.

Fire Prevention Plan – OSHA 29 CFR 1910.39 requires a written fire prevention plan be  made available to employees in workplaces that have more than 10 employees.  Oral plans may be communicated by employers with 10 employees or less.  Minimum elements of the plan must include the following:

  • A list of all major fire hazards, proper handling and storage procedures for hazardous materials, potential ignition sources and their control, and the type of fire protection equipment necessary to control each major hazard

  • Procedures to control accumulations of flammable and combustible waste materials

  • Procedures for regular maintenance of safeguards installed on heat-producing equipment to prevent the accidental ignition of combustible materials

  • The name or job title of employees responsible for maintaining equipment to prevent or control sources of ignition or fires

  • The name or job title of employees responsible for the control of fuel source hazards

An employer must inform employees when they are hired or when they change positions of the fire hazards to which they are exposed. An employer must also review with each employee those parts of the fire prevention plan necessary for self-protection.

Following are some select fire code requirements:

Powered Egress Doors
NFPA 101 “Life Safety Code®” Chapter 7.2.1.9 provides guidance on powered egress doors. These are doors in the path of egress that open upon the approach of a person or open with power assisted manual operation.  Powered egress doors must fail in a manually operable mode upon loss of power.  In the case of a powered egress door that is required to be self-closing,  it must be connected to the fire alarm system to drop out power upon detection of smoke on either side of that door.  Additionally, in the case of a powered egress door that must be self-latching, it is either self latching, or it becomes self- latching upon activation of a smoke detector on either side of that door.

Corridor Doors
NFPA 101 does not specify a maximum allowable gap for corridor doors and only specifies that the door must be “relatively smoke tight”.  In December of 2006, the “Healthcare Interpretations Task Force” (HITF) in an effort to further define the term “relatively” suggested maximum gaps for corridor doors:

  • The gap between the door edge and the frame shall not be greater than the depth of the door stop.

  • In a facility that is not fully sprinklered, a maximum gap of 1/4” between the face of the door and the door stop is suggested.

  • In a fully sprinklered facility, the suggested maximum gap increases to 1/2” between the face of the door and the door stop.

  • In the case of a two leaf door, there is no gap requirement or suggestion but rather the meeting edges must have an astragal, a rabbet, or a bevel.

Keep in mind, this does not apply to corridor doors of vertical opening, exits, and hazardous area which must meet the more stringent requirements of fire doors.

Sprinkler Flow and Obstruction Testing
NFPA 25 “Standard for the inspection, testing, and maintenance of water based fire protection systems” specifies in Chapter 13.2.1 the following:

“An investigation of piping and branch lines conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end of one branch line for the purpose of investigating for the presence of foreign organic and inorganic material”.

13.2.1.1 goes on to state:

“Alternative non-destructive methods shall be permitted”.

NFPA 25 Annex D describes in detail methods for testing, identification of materials that might be encountered during the investigation, and describes further actions to be taken if the inspection reveals the presence of foreign materials.

Fire Alarm Device Visual Inspection
NFPA 72 “National Fire Alarm Code®”  Table 10.3.1 lists frequencies of visual inspections for fire alarm equipment.  Many devices require semi-annual inspections including for example many initiating devices such as smoke and duct detectors, heat detectors, pull boxes, waterflow and supervisory devices.  Keep in mind that most of these devices also require an annual functional test that will include a visual inspection during the annual  testing while radiant energy heat detectors, waterflow devices, and valve tamper switches require semi-annual functional testing so the visual inspection would be conducted at that time.  The frequency of functional testing is listed in table 10.4.3.

Code Edition
The Joint Commission and the Center for Medicare and Medicaid (CMS) currently use the 2000 edition of the Life Safety Code®.  You should verify with your state and local Authority Having Jurisdiction (AHJ) which edition they have adopted.

For further information, please contact Geoff Gilbert at Capaccio Environmental Engineering, Inc. at 508.970.0033 x142 or by email at ggilbert@capaccio.com.

 

 

Back to Articles Back to Articles

Home | About Us | Services | Tools | Contact Us

© Copyright 1996-2009, Capaccio Environmental Engineering, Inc. All Rights Reserved